ATC Service Entrance Rated MCCB & Power Breaker Based ATS
ATC Service Entrance Rated MCCB & Power Breaker Based ATS
Cat® Service Entrance Rated (SER) automatic transfer switches (ATS) are designed to provide standby power emergency power to entire installation loads to protect against utility power interruption; yet allow the ATS to be as close as possible to the point of service entrance. By safely and in code compliance, integrating the necessary overcurrent protection and service disconnecting means into the automatic transfer switch, a single installation can be made at the service entrance. This design eliminates the need for a separate upstream fault protection and respective interconnections, which in turn reduces installation space, time, and cost. Breaker-based Service Entrance Rated transfer switches are available from 30A to 5000A.
Product Features
- ATC-100 on Residential & Light Commercial MCCB based, ATC-300+ or ATC-800 on MCCB & Power Breaker ATS products
- UL 1008 service entrance listed (up to 3200A)
- Service disconnect (both off) capability
- Integral over current protection
- Lockout when in disconnected position (only)
- Service entrance labeled
- Integrated Design
- Disconnecting neutral assembly
- Ground fault protection capability (all ratings)
(Required by code on rating 480V, and 1000A or higher) - Keyed service entrance switch
- Draw-out type breakers (available on Power Breaker ratings)
- UL 891 for 4000-5000A
- Loads protected against extended power loss
- Quick restoration of the circuit after a trip (versus a fused circuit that requires fuse availability)
- Trip on a fault prohibits transfer to the emergency source
- Fused circuit allows switch testing by simulating an actual power failure
- Lockable disconnect position permits safe downstream maintenance
Documents & Brochures
Standard Equipment
Controls and Wiring
- All controls relays and industrial grade relays are totally encapsulated to minimize exposure to dust and dirt. Lugs are 90º rated and all control wire is #16 AWG, type XLPE with a 125º temperature rating.
Enclosure
- Durable powder-coated steel NEMA 1, 3R or 12 enclosures with three door hinges to ensure proper support of the door and door mounted devices. The hinges have removable hinge pins to facilitate door removal for easy wall mounting or service and are supplied with pad-lockable latches.
Additional information
الملخص الفني - نطاق التقديرات | 30-5000 أمبير |
---|---|
الملخص الفني - نوع النقل | مفتوح / مغلق / مؤخر |
الملخص الفني - نوع المفتاح | العلبة المصبوبة وقاطع الطاقة |
المعدلات - MCCB | 30-1000 أمبير مع قطبين، و3، و4 أقطاب |
المعدلات - قاطع الطاقة الثابت | 200-3200 أمبير مع 2، أو 3، أو 4 أقطاب |
المعدلات - قاطع طاقة السحب | 200-5000 أمبير مع 2، أو 3، أو 4 أقطاب |
المعدلات - استخدام جهد النظام | 120-600 فولت من التيار المتردد، 50/60 هرتز |
المعدلات - المقاومة | (قاطع الطاقة) حتى 100 kAIC عند 3 دورات بجهد 600 فولت |
المعدلات - الاختبارات المنطبقة | <اعتماد حسب CSA C22.2 رقم 178</br><br> مدرج على UL 1008 حتى 3200 أمبير</br><br>4000 أمبير، و5000 أمبير مدرج على UL 891</br> |
Offering Type |