3512B (50 Hz) 1600 – 1875 kVA

3512B (50 Hz) Generator Set

Producing reliable power from 1600 to 1875 kVA at 50 Hz, our 3512B diesel generator sets are made to meet your mission critical, continuous, standby and prime applications. We’ve designed each to ISO 8528-5 transient response requirements and to accept 100% rated load in one step. Generator sets offer both low fuel consumption and low emission systems.

Cat Generator Set Package

  • Cat generator set packages have been fully prototype tested
  • Accepts 100% block load in one step and meets NFPA 110 loading requirements
  • Conform to ISO 8528-5 steady state and transient response requirements

Cat Diesel Engine

  • Reliable, rugged, durable design
  • Field-proven in thousands of applications worldwide
  • Four-stroke-cycle diesel engine combines consistent performance and excellent fuel economy with minimum weight

SR5 Alternator

  • Superior motor starting capability minimizes need for oversizing alternator
  • Designed to match performance and output characteristics of Cat diesel engines
  • Robust Class H insulation

Cat ECS Control Panel

  • User-friendly interface and navigation
  • Scalable system to meet a wide range of installation requirement
  • Expansion modules and site-specific programming for specific customer requirements

Cooling System

  • Designed to operate in standard ambient temperatures up to 50�C (122�F)
  • Contact your Cat Dealer for specific ambient and altitude capabilities

Certifications

  • IBC seismic certification
  • EU Declaration of Conformity
  • EU Declaration of Incorporation
  • EU Eurasian Conformity (EAC)

One Safe Source

  • Components used in the generator set are selected at the design stage to provide optimum package performance
  • The generator set is fully assembled at a Caterpillar facility following our quality guidelines
  • Each generator set package is tested before leaving the Caterpillar facility
  • Cat product support, including dealer service, parts and warranty covers the entire Cat power system

Worldwide Product Support

  • Cat dealers have over 1,800 dealer branch stores operating in 200 countries
  • Your local Cat dealer provides extensive post-sale support, including maintenance and repair agreements

Standard Equipment

Air Inlet System
  • Aingle element canister type air cleaner with service indicator
Air Inlet
  • Air cleaner
Cooling
  • Package mounted radiator (except C175)
Control Panel
  • Speed adjust
  • Oil pressure (psi, kPa or bar)
  • 4 Programmable relay outputs (Form A)
  • kVAr (per phase, average & percent)
  • Over/under frequency (81 o/u)
  • Operating hours
  • Accessory module data link
  • Text alarm/event descriptions
  • Amps (per phase & average)
  • DC volts
  • Frequency (Hz)
  • 2 Programmable relay outputs (Form C)
  • kVAr-hr (total)
  • Volts (L-L & L-N)
  • RPM
  • kW (per phase, average & percent)
  • Over/under voltage (27 / 59)
  • Environmental sealed front face
  • Controls:
  • Engine cool-down timer
  • Customer data link (Modbus RTU)
  • High coolant temperature
  • 2 Programmable digital outputs
  • Power factor (per phase & average)
  • 24 Volt DC operation
  • Overspeed
  • Alarm acknowledge
  • Lamp test
  • kW-hr (total)
  • Low coolant temperature
  • Emergency stop
  • Generator phase sequence
  • Auto/start/stop control
  • Cat ECS 100
  • Low oil pressure
  • Engine cycle crank
  • Programmable protective relaying functions:
  • Reverse power (kW) (32)
  • Generator mounted - rear facing
  • Digital indication for:
  • Overcurrent (50 / 51)
  • Warning/shutdown with common LED indication of shutdowns for:
  • kVA (per phase, average & percent)
  • Serial annunciator module data link
  • Emergency stop button
  • Reverse reactive power (kVAr) (32RV)
  • 6 Programmable digital inputs
  • Failure to start (overcrank)
  • Low coolant level
  • Communications
  • Coolant temperature
  • True RMS AC metering, 3 phase, +/-2% accuracy
Exhaust
  • Exhaust flange outlet
Fuel
  • Primary fuel filter with integral water separator
  • Secondary fuel filters
  • Fuel priming pump
Control System
  • Failure to start (overcrank)
  • Auto/start/stop control
  • Cat ECS 100
  • Lamp test
  • Emergency stop pushbutton
  • 4 programmable digital inputs
  • Volts (L-L & L-N)
  • Low coolant level
  • Overspeed
  • frequency (Hz)
  • Engine cycle crank
  • DC volts
  • Coolant temperature
  • Alarm acknowledge
  • True RMS AC metering, 3-phase, +/-2% accuracy
  • Communications
  • 24 Volt DC operation
  • Engine cool-down timer
  • RPM
  • Warnings/shutdown indicators
  • Digital indication for:
  • Oil pressure
  • Low oil pressure
  • Amps (per phase & average)
  • Speed adjust
  • Emergency stop
  • 4 programmable digital outputs
  • Operating hours
  • High coolant temperature
Generator
  • Matched to the performance and output characteristics of Cat engines
  • IP23 Protection
Power Termination
  • Busbar
Generator System
  • Internal excitation (IE)
  • NEMA Class H insulation
  • Caterpillar's digital voltage
    regulator (CDVR)
  • Class H temperature rise at 40C ambient
  • 3-phase voltage sensing
  • Busbar connections
  • min/max exciter
  • Random wound
  • 3 phase brushless, Salient pole
  • RFI suppression
  • Winding temperature detectors
  • 6 Lead
Literature
  • Operation & Maintenance Manual
  • Parts book
Cooling System
  • Coolant drain line with valve
  • Radiator fan and fan drive
  • Fan and belt guards
  • JWAC
  • Caterpillar extended life coolant. (Not included with packages without radiator, installed SF44CTS, shipped loose radiators or heat exchangers)
  • Coolant level sensors (Not included with packages without radiator)
Exhaust System
  • Dry exhaust manifold
  • Flanged faced outlet(s)
Fuel System
  • Flexible fuel lines - shipped loose
  • Secondary fuel filters
  • Fuel priming pump
  • Fuel cooler; not included with packages without radiator
Generators and Attachments
  • 6 Leads
  • Note: 1800 Frames are form wound, permanent magnet excitation (PMG), with winding temp detectors
  • Busbar connections, top center mounted, top cable entry
  • KVAR / PF modes
  • Internal excitation (IE)
  • Generator set packages include: Regulator (CDVR)
  • RFI suppression
  • Winding temperature detectors
  • NEMA Class H insulation
  • 50 Hz models: IEC standard hole pattern
  • Reactive droop capability
  • 3 Phase brushless, Salient pole
  • Exciter diode monitor
  • Min / max exciter limiter
  • Random wound
  • 3 Phase voltage sensing
  • LV
  • Class H temperature rise at 40C ambient (125C prime / 150C standby)
  • Caterpillar's digital voltage regulator (CDVR) includes:
Governing System
  • Woodward 2301A isochronous governor
Lube System
  • Lubricating oil
  • Fumes disposal
  • Integral lube Oil cooler
  • Oil drain lines and valve
  • Gear type lube oil pump
  • Oil filter, filler and dipstick
Mounting System
  • Rubber anti-vibration mounts - shipped loose
  • Rails - Engine/generator/radiator mounting
Starting / Charging System
  • 24 Volt electric starting motor
  • Battery and battery rack w/cables
  • Battery disconnect switch
General
  • Paint - Caterpillar yellow with high gloss black rails & radiator
  • RH service
  • SAE standard rotation
  • Flywheel and Flywheel housing-SAE No. 00

Additional information

Offering Type

Generator Set Specifications - Standby Rating

1875/1750 kVA

Generator Set Specifications - Prime Power Rating

1700/1600 kVA

Generator Set Specifications - Emissions/Fuel Strategy

Low Fuel, Low Emissions

Generator Set Specifications - Voltage

380 to 415 Volts

Generator Set Specifications - Frequency

50 Hz

Generator Set Specifications - Speed

1500 rpm

Generator Set Specifications - Duty Cycle

Standby, Mission Critical, Prime

Generator Set Specifications - Maximum Rating

1875 kVA

Generator Set Specifications - Minimum Rating

1600 kVA

Engine Specifications - Engine Model

3512B TA, V-12, 4-Stroke Water-Cooled Diesel

Engine Specifications - Bore

170 mm ( 6.69 in )

Engine Specifications - Stroke

215 mm ( 8.46 in )

Engine Specifications - Displacement

58.6 l ( 3576 in³ )

Engine Specifications - Displacement - HD

58.56 l ( 3576 in³ )

Engine Specifications - Compression Ratio

15.5:1 HD

Engine Specifications - Aspiration

TA

Engine Specifications - Fuel System

Electronic Unit Injection

Engine Specifications - Governor Type

ADEM™ A3

Generator Set Dimensions - Length - Minimum

5249 mm ( 206.6 in )

Generator Set Dimensions - Length - Maximum

5469 mm ( 215.3 in )

Generator Set Dimensions - Width - Minimum

1975 mm ( 77.8 in )

Generator Set Dimensions - Width - Maximum

2286 mm ( 90 in )

Generator Set Dimensions - Height - Maximum

2367 mm ( 93.2 in )

Generator Set Dimensions - Dry Weight - Genset (minimum)

11350 kg ( 25010 lb )

Generator Set Dimensions - Dry Weight - Genset (maximum)

12180 kg ( 26840 lb )

Engine Specifications - Stroke - HD

215 mm ( 8.46 in )