C4.4 | DE88E0
Cat Generator Set Package
- Cat generator set packages have been fully prototype tested
- Accepts 100% block load in one step and meets NFPA 110 loading requirements
- Conform to ISO 8528-5 steady state and transient response requirements
Cat Diesel Engine
- Reliable, rugged, durable design
- Field-proven in thousands of applications worldwide
- Four-stroke-cycle diesel engine combines consistent performance and excellent fuel economy with minimum weight
M-Frame Alternator
- Superior motor starting capability minimizes need for oversizing alternator
- Designed to match performance and output characteristics of Cat diesel engines
- Robust Class H insulation
GCCP Control Panel
- User-friendly interface and navigation
- Scalable system to meet a wide range of installation requirement
- Expansion modules and site-specific programming for specific customer requirements
Cooling System
- Designed to operate in standard ambient temperatures up to 55°C (131°F)
- Contact your Cat Dealer for specific ambient and altitude capabilities
Certifications
Fully prototype tested with certified torsional vibration analysis available
One Safe Source
- Components used in the generator set are selected based on seamless design integration to provide the optimum performance
- The generator set is fully assembled at a Caterpillar facility following our quality guidelines
- Each generator set package is tested before leaving the Caterpillar facility
- Cat product support, including dealer service, parts and warranty covers the entire Cat power system
World Wide Product Support
- Cat dealers have over 1,800 dealer branch stores operating in 200 countries
- Your local Cat dealer provides extensive post-sale support, including maintenance and repair agreements
Virtual Tours
Documents & Brochures
- Electric Power Ratings Guide
- DE88E0, 50 Hz 88.0 kVA, LC Frame, Low BSFC Emissions Compliant Spec Sheet
- DE88E0, 50 Hz 88.0 kVA, M Frame, Low BSFC Emissions Compliant Spec Sheet
- DE88E0, 50 Hz 88.0 kVA, R Frame, Low BSFC Emissions Compliant Spec Sheet
- Sound Attenuated Level 1 Enclosures 30 - 220 kVA (50 and 60 Hz)
- Sound Attenuated Level 2 Enclosures 24 - 220 kVA (50 and 60 Hz)
Standard Equipment
Control panel
- GCCP Control panel
Alternator and Alternator attachments
- 12 Leads
- IP23 Protection
- Voltage regulator (single phase sensing)
- Tower panel, IP22, bottom cable entry
- Segregated low voltage (AC/DC) wiring panel
- Circuit breaker, IEC, 3 Pole, mounted in tower panel
Governing system
- Mechanical governing system
Cooling system
- Radiator and cooling fan with guards
- Coolant drain line with valve
- Fan drive, battery charging alternator drive
- Caterpillar extended life coolant
Air inlet system
- Air cleaner; light duty with disposable element
Exhaust system
- Stub pipe, gaskets, raincap & SAE exhaust flange
- Industrial silencer
Fuel system
- Standard open set fuel tank/base
Lube system
- Lubricating oil
- Oil drain line with valve
Mounting system
- Captive linear vibration isolators
- Lifting provision and drag points
- Termination points for coolant and lube oil drain lines
Starting/charging system
- 12V Battery with rack & cables
General
- Engine and alternator pre-paint, Caterpillar yellow
Additional information
Offering Type | |
---|---|
Generator Set Specifications - Minimum Rating | 88 kVA |
Generator Set Specifications - Maximum Rating | 88 kVA |
Generator Set Specifications - Emissions/Fuel Strategy | Non Regulated |
Generator Set Specifications - Voltage | 220 to 415 Volts |
Generator Set Specifications - Frequency | 50 Hz |
Generator Set Specifications - Speed | 1500 rpm |
Generator Set Specifications - Duty Cycle | Standby, Prime |
Engine Specifications - Engine Model | Cat® C4.4 |
Engine Specifications - Bore | 105 mm ( 4.1 in ) |
Engine Specifications - Stroke | 127 mm ( 5 in ) |
Engine Specifications - Displacement | 3.3 l ( 201.4 in³ ) |
Engine Specifications - Compression Ratio | 17.25:1 |
Engine Specifications - Aspiration | Turbocharged |
Engine Specifications - Fuel System | Inline |
Engine Specifications - Governor Type | Mechanical |
Generator Set Dimensions - Length - Maximum | 1925 mm ( 75.8 in ) |
Generator Set Dimensions - Width - Maximum | 1120 mm ( 44.1 in ) |
Generator Set Dimensions - Height - Maximum | 1361 mm ( 53.6 in ) |
Generator Set Dimensions - Dry Weight - Genset (maximum) | 1058 kg ( 2332 lb ) |