C18 (60 Hz)
C18 Generator Set
The C18 diesel generator sets has been developed for mission critical, standby and prime applications. Producing reliable power from 455 to 600 ekW at 60 Hz, meeting ISO 8528-5 transient response requirements and built to accept 100 % rated load in one step. The engines are U.S. EPA Certified for Stationary Emergency Use Only (Tier 2 Nonroad Equivalent Emission Standards) Emissions / Fuel Strategy.
Cat Generator Set Package
- Cat generator set packages have been fully prototype tested
- Accepts 100% block load in one step and meets NFPA 110 loading requirements
- Conform to ISO 8528-5 steady state and transient response requirements
Cat Diesel Engine
- Reliable, rugged, durable design
- Field-proven in thousands of applications worldwide
- Four-stroke-cycle diesel engine combines consistent performance and excellent fuel economy with minimum weight
A-Frame Alternator
- Superior motor starting capability minimizes need for oversizing alternator
- Designed to match performance and output characteristics of Cat diesel engines
- Robust Class H insulation
GCCP 1.2 Control Panel
- User-friendly interface and navigation
- Scalable system to meet a wide range of installation requirement
- Expansion modules and site-specific programming for specific customer requirements
Cooling System
- Designed to operate in standard ambient temperatures up to 55°C (131°F)
- Contact your Cat Dealer for specific ambient and altitude capabilities
Certifications
UL2200 Listed; CSA 22.2; Certification of Compliance – IBC Seismic; Dual IBC & HCAI
One Safe Source
- Components used in the generator set are selected based on seamless design integration to provide the optimum performance
- The generator set is fully assembled at a Caterpillar facility following our quality guidelines
- Each generator set package is tested before leaving the Caterpillar facility
- Cat product support, including dealer service, parts and warranty covers the entire Cat power system
World Wide Product Support
- Cat dealers have over 1,800 dealer branch stores operating in 200 countries
- Your local Cat dealer provides extensive post-sale support, including maintenance and repair agreements
Documents & Brochures
- Electric Power Ratings Guide
- C18, 60 Hz, 550 ekW Standby, 500 ekW Prime, TIER II Non-Road Spec Sheet
- C18, 60 Hz, 550 - 570 ekW spec sheet
- C18, 60 Hz, 600 ekW Standby, 545 ekW Prime, TIER II Non-Road Spec Sheet
- C18, 60 Hz, 650 ekW Standby, 600 ekW Prime, TIER II Spec Sheet
- C18, 60 Hz, 700 ekW Standby, 635 ekW Prime, TIER II Spec Sheet
- C18, 60 Hz, 750 ekW Standby, 680 ekW Prime, TIER II Spec Sheet
- C18, 60 Hz, 750 ekW Standby, 680 ekW Prime, EPA TIER III Spec Sheet
- C18 for Industrial Applications
- GCCP 1.2 Control Panel Data Sheet
- GCCP 1.5 Control Panel Data Sheet
Standard Equipment
Air Inlet
- Air cleaner
Air Inlet System
- Turbocharger
- Light duty air cleaner
- Aftercooler core
Cooling
- Caterpillar extended life coolant
- Fan drive, battery charging alternator drive
- Coolant drain line with valve
- Radiator and cooling fan with guard
- Package mounted radiator
Exhaust
- Exhaust flange outlet
Exhaust System
- Stainless steel exhaust flex gaskets, raincap and SAE exhaust
flange for customer use - shipped loose
Fuel System
- Standard 8 hour open set fuel tank
Fuel
- Secondary fuel filters
- Fuel priming pump
- Primary fuel filter with integral water separator
Generator and Attachments
- Matched to the performance and output characteristics of Cat engines
- Segregated low voltage (AC/DC) wiring panel
- Power center, IP22
- A Frame generator - IP21 protection
- Integrated voltage regulator (IVR)
- Mandatory option circuit breaker, IEC, 3 pole, mounted in power centre
- Integrated voltage regulator (IVR)
Generator
- IP23 Protection
- Matched to the performance and output characteristics of Cat engines
- Load adjustment module provides engine relief upon load impact and improves load acceptance and recovery time
Power Termination
- Busbar
Control System
- GCCP 1.2
Governing System
- Cat electronic governor (ADEM A4)
Control Panel
- EMCP 4 Genset controller
Lube System
- Lubricating oil
- Oil drain valves
Mounting System
- Captive linear vibration isolators between base and engine-generator.
includes lifting provisions and termination points for coolant
and lube oil drain lines
Mounting
- Rubber vibration isolators
Starting/Charging
- 24 Volt battery with rack and cables
- 24 volt starting motor
- Batteries
General
- Engine and alternator pre-paint, Caterpillar yellow
- Paint - Caterpillar yellow except rails and radiators gloss black
Additional information
مواصفات مجموعة المولدات - أقصى معدل | 600 كيلووات كهربائي |
---|---|
مواصفات مجموعة المولدات - أدنى معدل | 455 كيلووات كهربائي |
مواصفات مجموعة المولدات - الانبعاثات/إستراتيجية الوقود | معتمد وفق معايير وكالة حماية البيئة (EPA) الأمريكية، من المستوى 2 |
مواصفات مجموعة المولدات - الجهد | 208 إلى 600 فولت |
مواصفات مجموعة المولدات - التردد | 60 هرتز |
مواصفات مجموعة المولدات - السرعة | 1800 دورة في الدقيقة |
مواصفات مجموعة المولدات - دورة العمل | الاحتياطية، والرئيسية |
مواصفات المحرك - موديل المحرك | C18 ATAAC ديزل، I-6، 4 أشواط ومبرد بالمياه |
مواصفات المحرك - التجويف | 145 مم ( 5.71 بوصة ) |
مواصفات المحرك - الشوط | 183 مم ( 7.2 بوصة ) |
مواصفات المحرك - الإزاحة | 18.1 بوصة³ ( 1106.4 l ) |
مواصفات المحرك - نسبة الانضغاط | 14.5:1 |
مواصفات المحرك - السحب | تبريد لاحق هواء إلى هواء |
مواصفات المحرك - نظام الوقود | حقن وحدة إلكتروني |
مواصفات المحرك - نوع المنظم | Adem™A4 |
أبعاد مجموعة المولدات - الطول - الحد الأقصى | 218.5 مم ( 5550 بوصة ) |
أبعاد مجموعة المولدات - العرض - الحد الأقصى | 2056 مم ( 80.9 بوصة ) |
أبعاد مجموعة المولدات - الارتفاع - الحد الأقصى | 2737 مم ( 107.8 بوصة ) |
Offering Type |
-
Enclosures
C13, C15, C18 SA enclosure. 350-600 kW 60 Hz
View Details -
Enclosures
C13, C15, C18 WP Enclosure. 350-600 kW 60 Hz
View Details -
Control Panels
EMCP 4.2B Control Panel
View Details -
Control Panels
EMCP 4.4 Control Panel
View Details