C32 (60 Hz)
C32 (60 Hz)
Producing reliable power from 830 to 1250 ekW at 60 Hz, our C32 diesel generator sets are made to meet your mission critical, continuous, standby and prime applications. We’ve designed each to ISO 8528-5 transient response requirements and to accept 100% rated load in one step. Generator sets range from low fuel consumption systems to EPA Stationary Emergency (Tier 2) certification.
Cat Generator Set Package
- Cat generator set packages have been fully prototype tested
- Accepts 100% block load in one step and meets NFPA 110 loading requirements
- Conform to ISO 8528-5 steady state and transient response requirements
Cat Diesel Engine
- Reliable, rugged, durable design
- Field-proven in thousands of applications worldwide
- Four-stroke-cycle diesel engine combines consistent performance and excellent fuel economy with minimum weight
SR5 Alternator
- Superior motor starting capability minimizes need for oversizing alternator
- Designed to match performance and output characteristics of Cat diesel engines
- Robust Class H insulation
EMCP 4 Control Panel
- User-friendly interface and navigation
- Scalable system to meet a wide range of installation requirement
- Expansion modules and site-specific programming for specific customer requirements
Cooling System
- Designed to operate in standard ambient temperatures up to 50°C (122°F)
- Contact your Cat Dealer for specific ambient and altitude capabilities
Certifications
- UL 2200 Listed
- CSA
- IBC seismic certification
- OSHPD pre-approval
One Safe Source
- Components used in the generator set are selected at the design stage to provide optimum package performance
- The generator set is fully assembled at a Caterpillar facility following our quality guidelines
- Each generator set package is tested before leaving the Caterpillar facility
- Cat product support, including dealer service, parts and warranty covers the entire Cat power system
Worldwide Product Support
- Cat dealers have over 1,800 dealer branch stores operating in 200 countries
- Your local Cat dealer provides extensive post-sale support, including maintenance and repair agreements
Videos
Virtual Tours
Documents & Brochures
- Electric Power Ratings Guide
- C32, 60 Hz, 1000 ekW Standby/MC, 910 ekW Prime, 830 ekW Cont., Low Fuel Consumption Spec Sheet
- C32, 60 Hz, 1000 ekW Standby/MC, 910 ekW Prime, 830 ekW Cont., U.S. EPA Certified for Emergency Stationary Applications (Tier 2) Spec Sheet
- C32, 60 Hz, 1250 ekW Standby/MC, 1136 ekW Prime, Low Fuel Consumption Spec Sheet
- C32, 60 Hz, 1250 ekW Standby/MC, 1136 ekW Prime, U.S. EPA Certified for Emergency Stationary Applications (Tier 2) Spec Sheet
- C27-C32 GC NA Enclosure data sheet
Standard Equipment
Air Inlet System
- Single element canister type with service indicator
Control Panel
- Warning shutdowns
- EMCP 4.2B
- Digital Indicators
- Communications
- Control features
- Programmable protective relaying functions
Cooling System
- Caterpillar extended life coolant
- ATAAC
- Coolant drain line with valve
- Low coolant level sensor
- Fan and belt guards
- Radiator fan and fan drive
Exhaust System
- 203 mm (8 in) ID round flanged outlet
- Exhaust manifold - dry
Fuel System
- Fuel cooler
- Fuel priming pump
- Secondary fuel filters
- Primary fuel filter with water separator
General
- RH service
- Caterpillar yellow with high gloss black rails & radiator
- SAE standard rotation
- Flywheel and flywheel housing-SAE
Generators and Attachments
- Class H temperature rise at 40C ambient
- 3 Phase brushless
- Permanent magnet excitation (PMG)
- Winding temperature detectors
- Integrated voltage regulator (IVR)
- Reactive droop
- IEC standard hole pattern
- NEMA Class H insulation
- Busbar connections, top center mounted, top cable entry
- Salient pole
- 6 Lead
- Internal excitation (IE)
Governing System
- ADEM(tm) A4
Lube System
- Gear type lube oil pump
- Oil drain lines and valve
- Fumes disposal
- Lubricating oil
- Integral lube Oil cooler
- Oil filter, filler and dipstick
Mounting System
- Rubber anti-vibration mounts
- Rails - Engine/generator/radiator mounting
Power Termination
- Busbar
Starting and Charging
- 45 Amp Charging alternator
- 24 Volt electric starting motor
- Battery disconnect switch
- Battery, rack and cables
Additional information
Offering Type | |
---|---|
Generator Set Specifications - Maximum Rating | 1250 ekW |
Generator Set Specifications - Minimum Rating | 830 ekW |
Generator Set Specifications - Emissions/Fuel Strategy | Low Fuel, Tier 2 Nonroad Stds |
Generator Set Specifications - Voltage | 220 to 4160 Volts |
Generator Set Specifications - Frequency | 60 Hz |
Generator Set Specifications - Speed | 1800 rpm |
Generator Set Specifications - Duty Cycle | Standby, Mission Critical, Prime, Continuous |
Engine Specifications - Engine Model | C32 TA, V-12, 4-Stroke Water-Cooled Diesel |
Engine Specifications - Bore | 145 mm ( 5.71 in ) |
Engine Specifications - Stroke | 162 mm ( 6.38 in ) |
Engine Specifications - Displacement | 32.1 l ( 1958.86 in³ ) |
Engine Specifications - Compression Ratio | 15.0:1 |
Engine Specifications - Aspiration | TA |
Engine Specifications - Fuel System | MEUI |
Engine Specifications - Governor Type | Adem™A4 |
Generator Set Dimensions - Length - Minimum | 4165 mm ( 164 in ) |
Generator Set Dimensions - Length - Maximum | 4385 mm ( 172.7 in ) |
Generator Set Dimensions - Width - Minimum | 1684 mm ( 66.3 in ) |
Generator Set Dimensions - Width - Maximum | 2228 mm ( 87.7 in ) |
Generator Set Dimensions - Height - Minimum | 2162 mm ( 85.1 in ) |
Generator Set Dimensions - Height - Maximum | 2194 mm ( 86.4 in ) |
Generator Set Dimensions - Dry Weight - Genset (minimum) | 6668 kg ( 14700 lb ) |
Generator Set Dimensions - Dry Weight - Genset (maximum) | 7600 kg ( 16755 lb ) |
-
Enclosures
C27 and C32 Sound Attenuated Enclosure
View Details -
Control Panels
EMCP 4.2B Control Panel
View Details -
Control Panels
EMCP 4.3 Control Panel
View Details -
Control Panels
EMCP 4.4 Control Panel
View Details